High-voltage shore power supply

Get a Quick Quote Whatsapp

    • The device supports both 60Hz and 50Hz power supply modes; within the permissible capacity range of shore power inverters, variations in various loads (capacitive, inductive, or hybrid loads) do not adversely affect the output power quality, with voltage and frequency being continuously adjustable.
    • The system shall feature a hard-wired interface and a communication interface with the shore power inverter to facilitate communication, as well as enable control of the shore power inverter, including but not limited to the following functions: information exchange, parameter monitoring, and alarm generation.
    • The rated output is a three-phase sinusoidal power supply, and its power quality meets the user’s requirements.
    • The control system is equipped with synchronization functionality for grid connection to the ship’s power supply.
    • The shore power inverter employs an IGBT-based four-quadrant active rectifier, ensuring that the aerospace shore power inverter system does not introduce reactive power losses to the grid, while maintaining a power factor identical to that of the grid side.
    • The shore power inverter features protection functions against under-voltage, over-voltage, over-current, and over-temperature; the shore power inverter equipment can operate continuously at full load when the ambient temperature is below 50 °C.
    modelAyA-331000AyA-332000AyA-333000AyA-335000AyA-338000
    power rating1000KVA2000KVA3000KVA5000KVA8000KVA
    Output Power Factor≥0.98
    operate modeSPWM method, with sine wave output.
    power input10 kV or 6.6 kV
    Input Phase NumberThree-phase four-wire system
    power output10 kV or 6.6 kV
    Output phase numberThree-phase four-wire system
    rated frequency50/60Hz
    Frequency accuracy≤0.1%
    frequency stability≤0.01%
    Output voltage regulation rateOutput voltage regulation: <1% (for load variations from 0 to 100%)
    Input/output voltage total harmonic distortion (THD)THDu<3%
    Three-phase phase difference120°±2°
    protectorShort-circuit protection, overload protection, overcurrent protection, overvoltage and undervoltage protection, phase sequence protection, transformer overheating protection, and reverse power protection.
    overload multiples120% (Duration: 60s)
    CICANopen, Profibus, etc.
    cooling-down methodwater-cooled
    productiveness≥97%
    Noise level≤70dB
    above sea level<2,000 meters
    work environmentOperating temperature: -30 ~ 50 °C (no capacity reduction); Relative humidity: ≤95% (no condensation).

    aviation ground support

    Aviation Ground Support

    Suitable for aircraft ground power systems and aviation maintenance operations.

    onshore power supply

    Onshore Power Supply

    Shore power supplies electricity to docked ships from land grids, replacing on-board generators to cut fuel consumption and emissions.

    variable frequency

    Variable Frequency

    Variable frequency power supply outputs adjustable voltage and frequency. It simulates global grid power for testing electrical equipment.

    military & defense

    Military & Defense

    Applicable to military electronic systems and specialized defense equipment testing.

    start your project with a reliable partner

    Start Your Project with a Reliable Partner

    Get high-quality products, fast turnaround, and competitive pricing tailored to your business needs.

    Get Support Now